Output Current; Output Voltage; Output Power - GE AF-600 FP Operating Instructions Manual

Lonworks
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

5.5 Network Variable Description - VSD Profile - Output
5.5.1 Drive Speed
Variable
SNVT
name:
type:
nvoDrvSpeed
SNVT_lev_percent
This variable contains the frequency converter speed as a percentage of the nominal speed.

5.5.2 Output Current

Variable
SNVT
name:
type:
nvoDrvCurnt
SNVT_amp
This variable contains the frequency converter output current in ampere measured as a mean value, IRMS.
The value is filtered and therefore approximately 1.3 seconds delayed before a current change is reflected in the output variable.

5.5.3 Output Voltage

Variable
SNVT
name:
type:
nvoDrvVolt
SNVT_volt
This variable contains the frequency converter output voltage.

5.5.4 Output Power

Variable
SNVT
name:
type:
nvoDrvPwr
SNVT_power_kilo
This variable contains the frequency converter output power in kW, calculated on the basis of the actual motor voltage and current.
The value is filtered and therefore approximately 1.3 seconds delayed before a power change is reflected in the output variable.
5.5.5 Running Hours
Variable
SNVT
name:
type:
nvoDrvRunHours
SNVT_time_hour
This variable contains the total running hours of the motor.
Value:
Min:
Max:
-163.840 %
+163.830 %
Value:
Min:
Max:
0 A
3,276.6 A
Value:
Min:
Max:
0 V
3,276.6 V
Value:
Min:
Max:
0 kW
6,554.4 kW
Value:
Min:
Max:
0 hr
65,534 hr
AF-600 FP LonWorks
Resolution:
0.005 %
5
Resolution:
0.1 A
Resolution:
0.1 V
Resolution:
0.1 kW
Resolution:
1 hr