Bindicator F78MP Series Installation & Operation Manual page 40

Air radar
Table of Contents

Advertisement

Code/Icon
Meaning
S:17
Calibration interval as defined in Mainte-
nance Required Limit has expired.
S:18
Calibration interval as defined in Mainte-
nance Demanded Limit has expired.
S:25
Internal error
S:27
Internal device failure caused by an External
RAM memory error.
S:28
Internal device failure caused by a RAM
memory error.
S:29
EEPROM damaged
S:30
EEPROM corrupt
S:31
Flash error
S:33
Factory calibration for the internal
temperature sensor has been lost.
S:34
Factory calibration for the device has
been lost.
S:48
User configuration is invalid. One or more
of parameters: Low Calibration Point, High
Calibration Point, Volume breakpoints, and/
or Auto False-Echo Suppression, are set to
invalid values.
S:52
Fail-Safe is activated. Possible causes:
1. hardware failure
2. memory failure
3. Fail-safe LOE timer expired-possible
causes: faulty installation, antenna material
build-up, foaming/other adverse process
conditions, invalid calibration range
S:54
Fault occurs when the PV exceeds the user
configured min./max. range for mA output.
S:66 to S:83
Device error. NOTE fault text and icons
appear only on LCD
S:94
Device error. Possible causes:
1. Voltage too low
2. Hardware defect
S:95 to 97
Device error. NOTE fault text and icons
appear only on LCD
S:98 to 108
Device error. NOTE fault text and icons
appear only on LCD
S:109 to 112
Device error. NOTE fault text and icons
appear only on LCD
Corrective Action
Perform calibration
Perform calibration
Reset power. If fault persists, contact Bindicator
Repair required, contact Bindicator
Repair required, contact Bindicator
Repair required, contact Bindicator
Reset power. If fault persists, contact Bindicator
Repair required, contact Bindicator
Repair required: contact Bindicator.
Repair required: contact Bindicator.
Reconfigure the unit.
Ensure the difference between High Cali-bration
Point and Low Calibration Point is not less than or
equal to zero; do a Master Reset.
For 1 and 2: if fault persists, contact Bindicator
For 3:
• Correct configuration; ensure installation is correct
• No antenna build-up
• Adjust process conditions to minimize adverse
conditions
• Correct calibration range
Adjust process to fall within limits of min./max. mA
values or adjust limits of mA if possible.
Repair required, contact Bindicator
For 1: Confirm voltage is within specifications and
modify wiring or increase source voltage accordingly
For 2: Require required, contact Bindicator
Repair required, contact Bindicator
Repair required, contact Bindicator
Repair required, contact Bindicator
36
www.bindicator.com
MPR180416 Rev. B