4.7.5 Reminder Activation: Allows you to enable a maintenance reminder
4.7.6 Service Interval: User-configurable recommended time between product inspections.
Value Range: 0 to 20 years; Default 1.0 years
4.7.7 Maintenance Status: Indicates which level of maintenance reminder is active.
4.7.8 Acknowledge Status: Indicates which level of maintenance reminder has been acknowledged.
4.7.9 Acknowledge: Acknowledges the current maintenance reminder.
1. Press RIGHT arrow key twice to open parameter view and activate EDIT mode
2. Press RIGHT arrow key to acknowledge the reminder
4.8 Calibration Schedule:
lifetime to the next calibration. You can modify the Total Calibration Interval, set schedules for maintenance reminders,
and acknowledge them.
4.8.1 Time since Last Calibration: Time elapsed since last calibration. Can be reset to zero after performing a service.
Can be reset locally by entering 0 into this parameter.
4.8.2 Time until Next Calibration: Read only. Calibration interval (4.8.6) less Time since Last Calibration (4.8.1)
4.8.3 Reminder 1 (Required): If Time Until Next Calibration (4.8.2) is equal or less than this value, the device generates
a Maintenance required reminder.
Value Range: 0 to 20 years; Default 0.164 years
4.8.4 Reminder 2 (Demanded): If Time Until Next Calibration (4.8.2) is equal or less than this value, the device ....
generates a Maintenance required reminder.
Value Range: 0 to 20 years; Default 0.019 years
4.8.5 Reminder Activation: Allows you to enable a maintenance reminder
4.8.6 Service Interval: User-configurable recommended time between product calibrations.
Value Range: 0 to 20 years; Default 1.0 years
4.8.7 Maintenance Status: Indicates which level of maintenance reminder is active.
4.8.8 Acknowledge Status: Indicates which level of maintenance reminder has been acknowledged.
4.8.9 Acknowledge: Acknowledges the current maintenance reminder.
1. Press RIGHT arrow key twice to open parameter view and activate EDIT mode
2. Press RIGHT arrow key to acknowledge the reminder
MPR180416 Rev. B
Timer OFF - Default
ON NO LIMITS
ON Reminder 1 (Maintenance Required) checked
ON Reminders 1 and 2 checked
ON Reminder 2 (Maintenance Demanded) checked
This device tracks calibration intervals on operating hours and monitors the predicted
Timer OFF - Default
ON NO LIMITS
ON Reminder 1 (Maintenance Required) checked
ON Reminders 1 and 2 checked
ON Reminder 2 (Maintenance Demanded) checked
31