4. Service
4.1 Demo Mode: Used to set up for demonstrations; reduces the time between measurements and the
accuracy for demonstration purposes.
Values: ON or OFF; Default OFF
4.2 Master Reset:
Following a reset to Factory Defaults, the LCD displays the Quick Start Wizard
Following a reset to Factory Defaults, complete reprogramming is required.
Resets all parameters to factory defaults, with certain exceptions. The list of exceptions include, but is not
limited to:
Language
Identification parameters (such as Tag, Installation Date)
Device Address
Write Protection
Auto False Echo Suppression
Auto False Echo Suppression Range
4.3 Powered Hours: Read only unless Write Protection (6.1) is set to Unlock (2457). Displays the number of
hours the unit has been powered up since manufacture.
4.4 Power-on Resets: Read only unless Write Protection (6.1) is set to Unlock (2457). The number of power
cycles that have occurred since manufacture.
4.5 LCD Backlight: Time the backlight remains on.
Range: 0 (backlight off ) to 128 seconds; Default 128 seconds
4.6 LCD Contrast: The factory setting is for optimum visibility at room temperature and in average light
conditions. Extremes of temperature will lesson the contrast.
Range: 0 to 20; Default 8 - Contrast setting will depend on ambient temperature.
4.7 Service Schedule: The device tracks service intervals based on operating hours and monitors the predicted
lifetime to the next service. You can modify the Total Service Interval, set schedules for maintenance reminders
and acknowledge them. The maintenance warnings and reminders are communicated to the end user
through status information. This information can be integrated into any Asset Management System.
4.7.1 Time since Last Service: Time elapsed since last service. Can be reset to zero after performing a service. Can be
reset locally by entering 0 into this parameter.
4.7.2 Time until Next Service: Read only. Service interval (4.7.6) less Time since Last Service (4.7.1)
4.7.3 Reminder 1 (Required): If Time Until Next Service (4.7.2) is equal or less than this value, the device generates a
Maintenance required reminder.
Value Range: 0 to 20 years; Default 0.164 years
4.7.4 Reminder 2 (Demanded): If Time Until Next Service (4.7.2) is equal or less than this value, the device generates a
Maintenance required reminder.
Value Range: 0 to 20 years; Default 0.019 years
30
www.bindicator.com
MPR180416 Rev. B