2.4 Rate
2.4.1 Reponse Rate: Sets the reaction speed of the device to measurement changes.
Response
Vessel Fill Rate/Min or Empty Rate/Min
Rate
SLOW
0.32 ft/min (0.1 m/min)
MED
3.28 ft/min (1.0 m/min)
FAST
32.8 ft/min (10.0 m/min)
Use a setting just faster than the maximum filling/emptying rate (whichever is faster).
2.4.2 Fill Rate/Min: Defines the maximum rate at which the reported sensor value is allowed to increase. Allows you
to adjust the unit response to increases in the actual material level. Fill Rate is automatically updated whenever
Response Rate is altered.
2.4.3 Empty Rate/Min: Defines the maximum rate at which the reported sensor value is allowed to decrease. Allows
you to adjust the unit response to increases in the actual material level. Fill Rate is automatically updated ..
whenever Response Rate is altered.
2.5 Fail-Safe
2.5.1 Material Level: Defines the mA output to use when the Fail-Safe Timer expires
HI
LO
HOLD
VALUE
2.5.2 Timer: Sets the time to elapse since the last valid reading, before the Fail-Safe Level is reported
Value Range: 0.00 to 720 s; Default 100 s
2.5.3 Level: Allows the user to define the mA value to be reported when the Fail-Safe timer expires.
Value Range: 3.56 mA to 22.6 mA; Default 3.56 mA
Response Rate
SLOW
MED
FAST
Response Rate
SLOW
MED
FAST
Last valid reading; Default; 22.6 mA
User selected value (Define in Level 2.5.3); Default 3.58 mA
Damping Filter
10 s
10 s
0 s
Fill Rate
0.32 ft/min (0.1 m/min)
3.28 ft/min (1.0 m/min)
32.8 ft/min (10.0 m/min)
Empty Rate
0.32 ft/min (0.1 m/min)
3.28 ft/min (1.0 m/min)
32.8 ft/min (10.0 m/min)
20.5 mA (max mA limit)
3.8 mA (min mA limit)
22
www.bindicator.com
MPR180416 Rev. B