Required SED2 Parameter Settings
The factory programs the following SED2 parameters before shipping. If these parameters
are changed or if the SED2 is ever reset to factory default, you must reset these parameters
as follows:
NOTE:
Required SED2 parameters for automatic bypass on a drive fault are as follows:
NOTE:
Siemens Building Technologies, Inc.
Parameter
P0704 in000
P0704 in001
P0732
Changing P0700 resets all digital inputs and P0704 will require programming.
Parameter
P0748
P0731
Follow wiring as noted in the NEMA Type 3R Bypass Operation Overview section
(Automatic Bypass Operation description).
Setting
3
3
52.2 (default)
Setting
52.3
Startup Procedures
51