Siemens SED2 VFD NEMA Operating Instructions Manual page 40

Bypass
Hide thumbs Also See for SED2 VFD NEMA:
Table of Contents

Advertisement

SED2 VFD NEMA Type 3R/3RHE Bypass Operating Instructions
Parameter
Description
P0010
Quick Commissioning
0 = Ready to Run
1 = Quick
Commissioning
30 = Factory Setting
NOTES:
1.
P0010 must always be set back to 0 before operating the motor.
2.
If P3900 is greater than 0 on completion of commissioning, P0010 is automatically set back to 0.
P0100
Operation for Europe/N.
America
0 = 50 Hz, kW (Europe)
factory default
1 = 60 Hz, hp
(North America)
2 = 60 Hz, kW
(North America)
The setting of Motor Frequency
and Unit of Measurement DIP
switch 2 overrides P0100
settings 0 and 1.
NOTES:
1.
Stop the SED2 (that is, disable all pulses) before changing this parameter.
2.
Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor
parameters (such as P0340, Calculation of motor Parameters).
32
Action
Press
to access parameter
1.
r0000 and to enter the SED2
parameter mode.
2.
Repeatedly press
advance to parameter P0010.
3.
Press
to access the
parameter values level.
4.
Press
to advance to 1.
5.
Press
to confirm and save
the P0010 = 1 setting.
1.
Press
to advance to
parameter P0100.
2
Press
to access the
parameter values level.
3.
Press
to advance to 1.
4.
Press
to confirm and save
the P0100 = 1 setting.
Setting/Default
Setting = 1
Default = 0
to
Setting = 1
Default = 0 or 1
(Default is determined
by the setting of the
motor frequency and
unit of measurement
DIP switches.)
Siemens Building Technologies, Inc.