Parameter
Description
P1000[0]**
Selection of Frequency
Setpoint
(Speed Command Source)
Selects the frequency setpoint
source as follows:
1 = Motor potentiometer
setpoint/BOP (keypad)
2 = Analog input
3 = Fixed frequency setpoint
4 = USS on BOP Link/AOP
5 = USS on COM link
6 = CB (Communications board
or module) on COM link/P1-N2
communications
P1000[1]**
Selection of Frequency
Setpoint
(Speed Command Source)
Selects the frequency setpoint
source as follows:
1 = Motor potentiometer
setpoint/AOP
2 = Analog input
3 = Fixed frequency
4 = USS on BOP Link/AOP
5 = USS on COM link
6 = CB (Communications board
or module) on COM link/P1-N2
communications
** Parameters have two index settings: IN000 = Auto and IN001 = Hand.
Siemens Building Technologies, Inc.
Action
1.
Press
to advance to
parameter P1000.
2.
Press
to access the
parameter indexes.
3.
Press
to advance to index
[0], IN000, AUTO.
4
Press
to confirm index
selection.
5.
Press
to advance to 2.
6.
Press
to confirm and save
the setting.
1.
Press
to advance to index
[1], IN001, HAND.
2.
Press
to confirm index
selection.
3.
Press
to advance to 1.
4.
Press
to confirm and save
the setting.
5.
Press
again to return to the
parameter selection level.
Startup Procedures
Setting/Default
Setting = 2
Default = 2
Setting = 1
Default = 1
37