Siemens SED2 VFD NEMA Operating Instructions Manual page 46

Bypass
Hide thumbs Also See for SED2 VFD NEMA:
Table of Contents

Advertisement

SED2 VFD NEMA Type 3R/3RHE Bypass Operating Instructions
Parameter
Description
P1080
Minimum Motor Frequency
0 Hz to 650 Hz
Minimum motor frequency at
which the motor will run
irrespective of the frequency
setpoint. This value applies to
both clockwise and
counterclockwise rotation.
P1082
Maximum Motor Frequency
0 Hz to 650 Hz
Maximum motor frequency at
which the motor will run
regardless of the frequency
setpoint. This value applies to
both clockwise and
counterclockwise rotation.
NOTE:
This value is limited internally to 200 Hz or five times the rated motor frequency (P0305). When P1300 is greater
than or equal to 20 (control mode = vector control), the value displays via r0209 (maximum frequency).
38
Action
1.
Press
to advance to
parameter P1080.
2.
Press
to access the
parameter values level.
3.
Press
to advance to
desired value.
4.
Press
to confirm and save
the setting.
1.
Press
to advance to
parameter P1082.
2.
Press
to access the
parameter values level.
3.
Press
to advance it desired
value.
4.
Press
to confirm and save
the setting.
Setting/Default
Site Setting
(20% to 30% Max)
Default = 10
Site Setting
Default = 50 or 60
(Default is determined
by the setting of the
motor frequency and
unit of measurement
DIP switches.)