Siemens SED2 VFD NEMA Operating Instructions Manual page 61

Bypass
Hide thumbs Also See for SED2 VFD NEMA:
Table of Contents

Advertisement

Drive Specification
Digital inputs (sink/source)
Analog inputs
Relay outputs
Analog outputs
Serial interface
Protection level
Temperature ranges
Humidity
Operational altitudes
Protection features
Standards
CE conformity
SED2 Compliance with EN61000-3-12:
NOTE:
From September 1st, 2005 all electrical apparatus covered by the EMC directive will have to
comply with EN61000-3-12 "Limits for harmonic currents produced by equipment connected to
public low voltage systems with input currents > 16A and =< 75 A per phase".
Siemens variable speed drives of the product range SED2 (Micromaster 436) fulfill the
requirements of the EN 61000-3-12 (without the need for external line reactors) regarding the
THD values of Table 3 under the pre condition of Rsce > 190. The required PWHD values will
not be achieved. Due to this fact it is recommended to apply for connection approval at the
local electricity board.
The local electricity board will evaluate among many other data the content of the 5th
harmonic current and the Line Power Factor "Lambda", which is the ratio of active power and
apparent power.
Siemens frequency inverters are optimized in design and operation characteristics regarding
energy efficiency and less interference with line supplies.
Siemens Building Technologies, Inc.
Table 9. Drive Specifications.
6: fully programmable and scalable isolated digital inputs, switchable
2: 0 to 10 Vdc, 0/4 mA to 20 mA , can also be configured as digital inputs
or
Ni 1000 input
2: configurable 30 Vdc/5A (resistive), 250 Vac 2A (inductive)
2: programmable (0/4 mA to 20 mA or 0V to 10 Vdc)
RS-485;
Protocols: Siemens, P1 and Johnson, N2;
Transmission rate: Up to 38.4k baud
IP20: NEMA Type 1 (with protective shield and gland plate installed)
IP54: NEMA Type 12 (400V and 500V series only)
Operating: 14°F to 104°F (–10°C to 40°C)
Storage: –40°F to 158°F (–40°C to 70°C)
95% rh, non-condensing
Up to 3280 ft (1000 m) above sea level without de-rating
Under-voltage, Over-voltage, Overload, Ground fault, Short circuit, Stall
prevention, Locked motor, Motor overtemperature l
temperature, Parameter PIN protection
UL, cUL
Conformity with EC Low Voltage Directive 73/23/EEC
Technical Specifications