Siemens SED2 VFD NEMA Operating Instructions Manual page 53

Bypass
Hide thumbs Also See for SED2 VFD NEMA:
Table of Contents

Advertisement

Automatic Restart Continued
Parameter
Description
P1211
Number of Restart Attempts
Specifies the number of times
SED2 will attempt to restart after
supply power brownout or fault, if
P1210 automatic restart is
activated.
P1212
Time to First Restart
Selects the time (seconds)
before the SED2 is restarted for
the first time if P1210 automatic
restart is activated.
P1213
Restart Time Increment
Selects the amount (seconds)
that the restart time is
incremented for each restart of
the SED2 if P1210 automatic
restart is activated.
Siemens Building Technologies, Inc.
Action
1.
Press
to enter the SED2
parameter mode and to r0000.
2.
Press
to advance to
parameter P1211.
3.
Press
to access the
parameter values level.
4.
Press
to advance to
desired value.
5.
Press
to confirm and save
the setting.
1.
Press
to enter the SED2
parameter mode and to r0000.
2.
Press
to advance to
parameter P1212.
3.
Press
to access the
parameter values level.
4.
Press
to advance to
desired value.
5.
Press
to confirm and save
the setting.
1.
Press
to enter the SED2
parameter mode and to r0000.
2.
Press
to advance to
parameter P1213.
3.
Press
to access the
parameter values level.
4.
Press
to advance to
desired value.
5.
Press
to confirm and save
the setting.
Startup Procedures
Setting/Default
Minimum = 0
Default = 3
Maximum = 10
Suggested = 10
Minimum = 0
Default = 3
Maximum = 10
Suggested = 10
Minimum = 0
Default = 30
Maximum = 1000
Suggested = 10
45