Parameter
Description
P0311*
Rated Motor Speed
0 to 40,000 1/min
Rated motor speed (rpm) from
motor nameplate.
A setting of 0 causes an internal
calculation of this value.
Vector control and V/f control
with speed controller require this
value.
Slip compensation in V/f control
requires this value for correct
operation.
Pole pair number is recalculated
automatically if the parameter is
changed.
P0640
Motor Overload Factor
10% to 400%
Limited to the maximum SED2
output current rating, or to 400%
of the rated current (P0305),
whichever is lower.
NOTE:
This parameter is available when
P0003 = 3 and
P0010 = 1
* Motor related parameters.
Siemens Building Technologies, Inc.
Action
1.
Press
to advance to
parameter P0311.
2.
Press
to access the
parameter values level.
3
Press
to advance to
nominal motor speed.
4.
Press
to confirm and save
the setting.
1.
Press
to advance to
parameter P0640.
2.
Press
to access the
parameter values level.
3.
Press
to advance to
desired value.
4.
Press
to confirm and save
the setting.
Startup Procedures
Setting/Default
Setting =
Motor nameplate
Default =
Varies by model
Setting =
As applicable
Default = 110
35