Parameter
Description
P0304*
Rated Motor Voltage
10V to 2000V.
Rated motor voltage (V) from
motor nameplate.
P0305*
Rated Motor Current
0A to 10,000A.
Rated motor current (A) from
motor nameplate.
P0307*
Rated Motor Power
0 kW or hp to 200 kW or hp.
Rated motor power (kW or hp)
from motor nameplate.
If P0100 = 1 (60 Hz, hp, North
America), then motor power is in
hp.
* Motor related parameters.
Siemens Building Technologies, Inc.
Action
1.
Press
to advance to
parameter P0304.
2.
Press
to access the
parameter values level.
3.
Press
to advance to
nominal voltage.
4.
Press
to confirm and save
the setting.
1.
Press
to advance to
parameter P0305.
2.
Press
to access the
parameter values level.
3.
Press
to advance to
nominal current.
4.
Press
to confirm and save
the setting.
1.
Press
to advance to
parameter P0307.
2.
Press
to access the
parameter values level.
3.
Press
to advance to
nominal power.
4.
Press
to confirm and save
the setting.
Startup Procedures
Setting/Default
Setting =
Motor nameplate
Default =
Varies by model
Setting =
Motor nameplate
Default =
Varies by model
Setting =
Motor nameplate
Default =
Varies by model
(hp/voltage dependent)
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sed2 vfd nema 3rSed2 vfd nema 3r harsh environment