SED2 VFD NEMA Type 3R/3RHE Bypass Operating Instructions
Parameter
Description
P3900
End Quick Commissioning
0 = End without motor calculation
or factory reset.
1 = End with motor calculation
and factory reset (recommended
on SED2 without bypass option).
2 =End with motor calculation
and with I/O reset.
3 =End with motor calculation but
without I/O reset (recommended
with SED2 with bypass option).
NOTES:
1.
P0010 must always be set back to 0 before operating the motor.
2.
If P3900 is greater than 0 on completion of commissioning, P0010 is automatically set back to 0.
3.
If P0700 either indeed was changed during this process, programming of P0704 = 3 is required.
40
Action
1.
Press
to advance to
parameter P3900.
2.
Press
to access the
parameter values level.
3.
Press
to advance to 1.
4.
Press
to confirm the
setting.
Setting/Default
Setting = 1
Default = 0