Table 6. Wire Sizes and Tightening Torques for NEMA Type 3R/3RHE Bypasses with 500V - 600V
Bypass
Enclosure
Part Number
Frame
Size
VBA40.5_3__X & HT1 ABC
VBA40.7_3__X & HT1 ABC
VBA41.0_3__X & HT1 ABC
VBA41.5_3__X & HT1 ABC
VBA42.0_3__X & HT1 ABC
VBA43.0_3__X & HT1 ABC
VBA45.0_3__X & HT1 ABC
VBA47.5_3__X & HT1 ABC
VBA410._3__X & HT1 ABC
VBA415._3__X
ABC
VBA415._3__XHT1
DE
VBA420._3__X
ABC
VBA420._3__XHT1
DE
VBA425._3__X & HT1 DE
VBA430._3__X & HT1 DE
VBA440._3__X & HT1 DE
VBA450._3__X
DE
VBA450._3__XHT1
F
VBA460._3__X
DE
VBA460._3__XHT1
F
VBA475._3__X & HT1 F
VBA4100_3__X
F
VBA4125_3__X
F
* Wire Size in AWG unless noted otherwise. Use Copper (Cu) wire that is rated 167°F (75°C) minimum, 600
Vac.
Siemens Building Technologies, Inc.
Disconnect
Switch
HP
kW
Amps
Wire
Size *
0.5 0.37 .9
14-8
35 (4)
0.7 0.55 1.3
14-8
35 (4)
1.0 0.75 1.4
14-8
35 (4)
1.5 1.1
2.1
14-8
35 (4)
2.0 1.5
2.7
14-8
35 (4)
3.0 2.2
3.9
14-8
35 (4)
5.0 4.0
6.1
14-4
35 (4)
7.5 5.5
9
14-4
35 (4)
10
7.5
11
14-1
50 (4)
15
11.0 17
14-4
35 (4)
15
11.0 17
14-1
50 (4)
20
15.0 22
14-4
35 (4)
20
15.0 22
14-4
35 (4)
25
18.5 27
14-1
50 (5.6)
30
22.0 32
14-1
50 (5.6)
40
30.0 41
14-1
50 (5.6)
50
37.0 52
14-1
50 (5.6)
6 - 350
120 - 275
50
37.0 52
kcmil
(14 - 31.1)
22 - 27
60
45.0 62
12-1
(2.5 - 3.1)
6 - 350
120 - 275
60
45.0 62
kcmil
(14 - 31.1)
6 - 350
120 - 275
75
55.0 77
kcmil
(14 - 31.1)
6 - 350
120 - 275
100 75.0 99
kcmil
(14 - 31.1)
6 - 350
120 - 275
125 90.0 125
kcmil
(14 - 31.1)
Drive.
Overload
Torque,
Torque,
Wire
lb-in
lb-in
Size *
(Nm)
(Nm)
7 - 10.3
18-14
(8 - 1.2)
7 - 10.3
18-14
(8 - 1.2)
7 - 10.3
18-14
(8 - 1.2)
7 - 10.3
18-14
(8 - 1.2)
7 - 10.3
18-14
(8 - 1.2)
7 - 10.3
18-14
(8 - 1.2)
7 - 10.3
18-14
(8 - 1.2)
7 - 10.3
18-14
(8 - 1.2)
7 - 10.3
18-14
(8 - 1.2)
18 - 22
14-10
(2 - 2.5)
18 - 22
14-10
(2 - 2.5)
18 - 22
14-10
(2 - 2.5)
18 - 22
14-10
(2 - 2.5)
27 - 40
18-3
(3.1 - 4.5)
27 - 40
18-3
(3.1 - 4.5)
27 - 40
18-3
(3.1 - 4.5)
27 - 40
18-3
(3.1 - 4.5)
27 - 40
18-3
(3.1 - 4.5)
36 - 53
10-1/0
(4.1 - 6)
36 - 53
10-1/0
(4.1 - 6)
36 - 53
10-1/0
(4.1 - 6)
36 - 53
10-1/0
(4.1 - 6)
124 - 210
10-1/0
(14 - 23.7)
Installation
Ground Lug
Max
Torque,
Range,
Backup
Wire
lb-in
Amps
Fuse,
Size *
(Nm)
Amps
.7 - 1.0
4
14-2
35 (4)
.9 - 1.25 5
14-2
35 (4)
1.1 - 1.6 6
14-2
35 (4)
1.8 - 2.5 10
14-2
35 (4)
2.2 - 3.2 12
14-2
35 (4)
2.8 - 4
16
14-2
35 (4)
4.5 - 6.3 25
14-2
35 (4)
7 - 10
40
14-2
35 (4)
9 - 2
45
14-2
35 (4)
14 - 20
80
14-2
35 (4)
14 - 20
80
14-2
35 (4)
17 - 22
80
14-2
35 (4)
17 - 22
80
14-2
35 (4)
22 - 32
125
14-2
35 (4)
28 - 40
150
14-2
35 (4)
36 - 45
175
14-2
35 (4)
40 - 50
200
14-2
35 (4)
40 - 50
200
14-2/0 35 (4)
45 - 63
250
14-2
35 (4)
45 - 63
250
14-2/0 35 (4)
70 - 90
350
14-2/0 50 (5.6)
80 - 100 400
14-2/0 50 (5.6)
50 - 200 800
14-2/0 50 (5.6)