Reset To Factory Defaults - Siemens SED2 VFD NEMA Operating Instructions Manual

Bypass
Hide thumbs Also See for SED2 VFD NEMA:
Table of Contents

Advertisement

SED2 VFD NEMA Type 3R/3RHE Bypass Operating Instructions

Reset to Factory Defaults

Parameter
Description
P0010
Reset to Factory Default
P0970
Resets SED2 parameters to the
factory defaults.
NOTES:
1.
First set P0010=30.
2.
Stop SED2 (that is, disable all pulses) before you reset parameters to factory default values.
3.
The following parameters retain their values after a factory reset:
P0918 (address of CB, communications board or module)
P2010 (USS baud rate)
P2011 (USS address)
4.
The reset process takes about 10 seconds.
50
Action
1.
Press
to enter the SED2
parameter mode and to r0000.
2.
Press
to advance to
parameter P0010.
3.
Press
to access the
parameter values level.
4.
Press
to advance to 30.
5.
Press
to confirm and save
the setting.
6.
Press
to go to parameter
P0970.
7.
Press
to access the
parameter values level.
8.
Press
to advance to 1.
9.
Press
to confirm and save
the setting.
Setting/Default
P0010:
Setting = 30
Default = 0
P0970:
Setting = 1
Default = 0
Siemens Building Technologies, Inc.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sed2 vfd nema 3rSed2 vfd nema 3r harsh environment

Table of Contents