System and site requirements
Table 7
Recommended wire size
Size (AWG)
6
8
10
553-3021-210
Standard 7.00
The minimum size of the conductors required between the DC source and the
Junction box is shown in Figure 7 on page 52.
Size (Metric)
#40
#35
#25
Connect these components together as shown in Figure 18. Make sure the
Option 11C main cabinet ground post is connected to the building ground
reference by a minimum AWG #6 (metric #40) insulated conductor. Connect
the input terminals of the NTAK28 Junction box to a clean DC power source
meeting the requirements shown in Table 6 on page 51.
January 2002
Maximum Length (one way)
50 ft (15 m)
30 ft (9 m)
20 ft (6 m)