Solenoids are not turning on,
or turning on then over time
turn off
Digital input will not energize
DOC-001041 / v1.0
1. Ensure the solenoid is wired correctly and to the
appropriate terminals.
To ensure proper solenoid wiring, a multi-meter in
OHM mode can be used to measure the resistance
between the + and – terminal of the associated output.
Note: this measurement should be done with the BMS
card powered off.
If properly wired, the multi-meter should read a
resistance of the solenoid coil plus the run length (i.e. if
the multimeter reads open, there is likely a problem
with wiring).
1. Ensure the PWM setting is correct for the appropriate
solenoid.
If using a peak-and-hold solenoid, the appropriate
PWM setting can be found in the solenoid data sheet.
Typically add a margin of 5-10% to allow for
temperature variance
If using a non-peak-and-hold solenoid, ensure the
PWM setting is set to 100%
1. Ensure the input is properly wired. See section 4 for
Interfacing / Wiring configurations.
2. In the case of a dry contact, ensure the PWR terminal is
connected and is sourcing the correct voltage.
3. Ensure adequate amount of wetting current is being
applied to through contact.
Run a current meter in series with the digital input
switch and verify the energized state meets the
requirements outlined in the "Electrical and Mechanical
Ratings" section of this document.
If there is not adequate wetting current, the digital
input either has too high of an impedance or the wiring
has been compromised.