BMS CARD ELECTRICAL RATINGS
I/O Type
Powered Output
Powered Output
Ionization I/O
Start/Stop
Switch
Digital Input
DOC-001041 / v1.0
Terminals
15-16 (Pilot 1) 19-20 (SSV)
17-18 (Pilot 2) 21-22 (SSV)
55-56 (Coil Pilot 1)
59-60 (Coil Pilot 2)
53-54 (Ion Pilot 1)
57-58 (Ion Pilot 2)
Switch Internal (IGN, RUN,
PWR)
7-8 (Press. High) 11-12
(PoC)
33-34 (ESD) 35-36 (Start)
Electrical Rating
12 / 24VDC, 5A Max
Expected Load: Inductive /
Resistive
12 / 24VDC Pulsed Output [PWM]
Expected Load: Inductive
Intermittent 80-130 VRMS Output @
5kHz (with 20kΩ source resistance)
Power: 3.3V (1kΩ source
resistance)
Ignite / Run: 3.3VDC Max (~10kΩ
load)
Energized State: 10VDC, 1.25mA
Min
De-energized State: 3VDC, 500uA
Max
30 VDC Max
Wire Gauge
/ Torque
12-30 AWG
0.5-0.6 Nm
12-30 AWG
0.5-0.6 Nm
12-30 AWG
0.5-0.6 Nm
12-30 AWG
0.5-0.6 Nm
12-30 AWG
0.5-0.6 Nm