TEMPERATURE INPUTS
There are four distinct temperature inputs available: Bath, Outlet, Stack, and Aux. The Bath, Outlet, and Stack
inputs are configurable to accept either a Type-K thermocouple or a PT-100 RTD sensor. The Aux temperature
input on terminals 43-44 is intended to be connected to a temperature sensor with a 4-20mA interface.
The Bath input is mandatory and must be connected to a Dual Element temperature sensor. The Outlet, Stack,
and Auxiliary temperature inputs are optional and can be utilized to monitor secondary process temperatures
such as the outlet temperature on a line heater. Unused temperature input terminals can be left unconnected.
When wiring thermocouples, Type-K thermocouple extension wire must be utilized to avoid cold junctions,
leading to inaccurate readings.
Below are the wiring diagrams for the Type – K Thermocouple and the RTD Temperature inputs.
Input
Terminals
Bath
61-66
Outlet
67-69
Stack
70-72
Aux
43-44
DOC-001041 / v1.0
Type
PT-100 RTD or Type-K Thermocouple
Dual Element or Single Element
PT-100 RTD or Type-K Thermocouple
Single Element
PT-100 RTD or Type-K Thermocouple
Single Element
4-20mA Transmitter
Modes Supported
High Temp ESD
Process Control
Disabled
High Temp ESD
Process Control
Display Only
Disabled
High Temp ESD
Display Only
Disabled
High Temp ESD
Process Control
Display Only
15