3.2 DIP-Switch SW 1 and SW 2 Settings

The two DIP-switches located on the circuit board are used to program the operator to operate in various modes and to turn on
or off various operating features. Whenever a switch setting is changed, power to the operator must be turned OFF and then
turned back on for the new setting to take affect. Check and review ALL switch settings prior to applying power to the operator.
Left 3 Switches - SW 2
SW 2 is Upside-Down on Circuit Board.
Switch
Function
Changes the direction the operator
1
will open/close the gate.
Auto-Close
2
Timer
Exit Loop Port
Output
3
Full Open Input
Relay Activation
and
4 and 5
LED Indicator
Light Activation
Warn Before
6
Operate
Reverses Gate
7
Stops Gate
Quick-Close
8
Timer Override
Switch
Function
Self-Test
1
Gate Opens
2
Uphill
Gate Opens
3
Downhill
16
Typical
Settings
SW 1 - Right 8 Switches
Setting
Opening direction
using ON setting.
Auto-close timer is OFF. Manual input required to close gate.
OFF
Auto-close timer is ON. Adjustable from 1-23 seconds to close gate.
ON
The output wired to terminal #4 becomes the output from the exit loop detector
OFF
plugged into the EXIT Loop port.
ON
Normal Setting. Terminal #4 is a normal full open input.
Relay activates and LED is ON when the gate is fully open.
4-OFF
5-OFF
Relay activates and LED is ON when the gate is not closed.
4-OFF
5-ON
Relay activates and LED is ON when the gate is opening and open.
4-ON
5-OFF
Relay activates and LED is ON when the gate is opening and closing.
4-ON
5-ON
Internal alarm will NOT sound.
OFF
Internal alarm will sound before gate starts and throughout gate's cycle.
ON
Normal Setting. Input to terminal #6 and/or reverse loops will REVERSE gate
OFF
during CLOSE cycle.
ON
Input to terminal #6 and/or reverse loops will STOP gate during CLOSE cycle.
OFF
Normal Setting. Timer will function normally.
Opening gate will stop and begin to close as soon as all reversing inputs (Reverse
ON
loops, photo sensors) are cleared regardless of the distance the gate has opened.
SW 2 - Left 3 Switches
Setting
OFF
Normal Setting. Normal gate operation.
ON
Self-test mode. Operator MUST be disconnected from gate to run self-test.
OFF
Normal Setting. Level gate operation or gate opens DOWNHILL.
ON
MUST be ON if gate opens UPHILL.
OFF
Normal Setting. Level gate operation or gate opens UPHILL.
MUST be ON if gate opens DOWNHILL.
ON
SW 1 - Right 8 Switches
SW 1 is Upside-Down on Circuit Board.
Description
Opening direction
using OFF setting.
Description
9510-065-D-5-20