Section 2 - Ac Power To Operator(S); High Voltage Wire Runs - DoorKing 9500 Series Installation & Owner's Manual

Maximum security heavy-duty vehicular slide gate operator
Hide thumbs Also See for 9500 Series:
Table of Contents

Advertisement

SECTION 2 - AC POWER TO OPERATOR(S)

Before attempting to connect any wiring to the operator, be sure that the circuit breaker in the electrical panel is in the OFF
position. Permanent wiring must be installed to the operator as required by local electrical codes. It is recommended that a
licensed electrical contractor perform this work.
Since building codes vary from city to city, we highly recommend that you check with your local building department prior
to installing any permanent wiring to be sure that all wiring to the operator (both high and low voltage) complies with local
code requirements.
Typical Grounding Sources
IMPORTANT: Ground wire shown without safety protection for clarity. Make sure ground wire is protected from being touched or electrical
shock could occur!

2.1 High Voltage Wire Runs

The 9500 draws significant power and should have a "Dedicated" circuit breaker at the power source.
If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large
gauge wire is used, a separate junction box must be installed for the operator connection. The wire table is based on stranded
copper wire. Wire run calculations are based on the NEC recommended maximum 3% voltage drop on the power line, plus an
additional 10% reduction in distance to allow for other losses in the system.
Never
run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.
This table illustrates the high voltage AC power wire size and distance limitations.
5 HP: 208 VAC
5 HP: 230 VAC
5 HP: 460 VAC
7 HP: 208 VAC
7 HP: 230 VAC
7 HP: 460 VAC
10 HP: 208 VAC
10 HP: 230 VAC
10 HP: 460 VAC
"Optional" Heater Installation Note: When installing a heater, refer to the "high voltage AC power wire size
and distance limitations" table on the instruction sheet with the heater kit for AC power wire run limitations.
9510-065-D-5-20
THIS GATE OPERATOR MUST BE PROPERLY GROUNDED!!
Ground to existing electrical system.
Phase
Amps
3
12.9
3
12.8
3
6.4
3
22.6
3
20.5
3
10.2
3
26.0
3
23.0
3
12.0
Ground
Wire
Ground to metallic cold water pipe.
Wire Size / Max Distance in Feet
12 AWG
10 AWG
140
225
155
250
630
1005
95
155
120
190
495
780
70
110
85
135
330
530
Ground
Wire
Grounding rod 10 feet in soil.
8 AWG
6 AWG
375
565
415
630
1680
2520
265
395
320
480
1300
1940
170
280
220
350
845
1350
13