DoorKing 1175 Installation & Owner's Manual
DoorKing 1175 Installation & Owner's Manual

DoorKing 1175 Installation & Owner's Manual

Commercial overhead gate/door operator
Hide thumbs Also See for 1175:

Advertisement

Quick Links

Installation/Owner's Manual
Use this manual for circuit board 4405-018 Revision A or higher.
Set so operator cycles OPEN upon initial power up and
MONITORED CONNECTIONS
3-Button Control
1
open command.
Close Beam Reverse (Term 2)
MUST be connected!
Open
2
OFF Not Used.
ON
Close
Stop
**
3
OFF Term 4 is Exit Loop Logic Output.
1 Open Beam Stop
ON Term 4 is Full Open Input (Normal Setting)
2 Close Beam Reverse
Common
4
OFF Auto-Close Timer is OFF.
ON Auto-Close Timer is ON (Normal Setting).
3 Open Edge/Beam Reverse
Normal
4 Close Edge/Beam Reverse
3-But
5
OFF Not Used.
5 Low Voltage Common
Set jumper to NORMAL when 3-button is not
6
OFF Not Used.
6 Low Voltage Common
used. Set to 3-BUT when a 3-button control
station with a N/C stop circuit is used.
***
7&8
Switches 7 & 8 work in conjunction with each other and
determine when the relay will activate. See manual.
1
OFF Not Used.
ON
1 2 3 4
2
OFF Not Used.
1
Open Beam Stop
2
Close Beam Reverse
3
OFF Not Used.
3
Open Edge/Beam Reverse
4
Close Edge/Beam Reverse
Radio
4
ON Switch MUST be ON for Model 1175.
Fire
Receiver
Dept
1
2
3
DKS
Low Voltage Common 1
Exit
Loop
Full Open 2
Detector
* 24 VAC 3
* Limited to 250 ma Max.
SW1
** Loop Out or Full Open 4
** Dependant on SW1, switch 3.
Timer
0-23 Sec
Partial Open 5
SW2
Reverse 6
Min
Max
Gate Tracker Data 7
Monitored
Gate Tracker Busy 8
External
Relay Contact
Connection
Not Used 9
Inputs
*** Dry Relay Contact 10
*** Operation of the relay is
dependent on SW1, switchs 7 & 8.
*** Dry Relay Contact 11
See manual for mor information.
Low Voltage Common 12
Activating
DKS
Low Voltage Common 13
Device(s)
Reverse
Loop
Alarm 14
Terminals 14 – 20 are
Detector
Reset 15
reserved for internal
operator wiring:
Not Used 16
no user connections.
Not
Rev
Used
Sens
Motor 17
Motor 18
CAUTION
Terminals 16–20
Circuit Board Pwr 19
High Voltage!
Circuit Board Pwr 20
Min Max Min Max
CAUTION – High Voltage!
Input Power
115 VAC Only
Model 1175 Operator
NEUTRAL
WHITE
Model 4405-010 Control Board
HOT
BLACK
GREEN
Ground
Power
Reset
P/N 1150-006 D 2/17
Switch
Button
Conforms To UL STD 325
Certified To CSA STD C22.2 # 247
Commercial Overhead Gate/Door Operator
THIS PRODUCT IS TO BE INSTALLED AND SERVICED BY A TRAINED GATE/DOOR SYSTEMS TECHNICIAN ONLY.
Visit www.dkslocator.com to find a professional installing and servicing dealer in your area.
Date Installed:
Installer/Company Name:
Phone Number:
Circuit Board
Serial Number
and Revision Letter:
Leave Manual with Owner
Copyright 2018 DoorKing, Inc. All rights reserved.
Copyright 2017 DoorKing, Inc. All rights reserved.
Model 1175
Model 1175
Model 1175
EXTERNAL ENTRAPMENT PROTECTION MUST be
installed or the gate/door operator WILL NOT function.
UL 325 August 2018 Standard
THIS PRODUCT IS FOR INDOOR USE ONLY.
Install in a protected area NOT exposed to weather.
Copyright 2009 DoorKing, Inc. All rights reserved.
1175-065-H-8-18

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 1175 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for DoorKing 1175

  • Page 1 OFF Not Used. Open Beam Stop Close Beam Reverse OFF Not Used. Open Edge/Beam Reverse Close Edge/Beam Reverse Radio Circuit Board ON Switch MUST be ON for Model 1175. Fire Receiver Dept Low Voltage Common 1 Exit Loop Full Open 2...
  • Page 2: Quick Guide: Dip-Switches

    Magnetic lock Magnetic lock is used and connected to terminals 9 and 13. See page 17 for wiring. Switch 3 MUST be in ON Position. Switch 4 MUST be turned OFF for Model 1175 operator. Leave in OFF position. Switch 1 If a magnetic lock is not used with the gate/door operator, leave this switch in the OFF position.
  • Page 3: Quick Guide: Terminal Descriptions

    Close LED Close N.O. floor and at least 6 ft from gate/door. Stop LED Stop N.C. See page 13 for info about installation. (DoorKing’s 3-wire 3-button control Common station cannot be used) 3-Pin with • When using a 3-button control •...
  • Page 4: Specifications

    ** Dependant on SW1, switch 3. Timer 0-23 Sec Partial Open 5 Reverse 6 Gate Tracker Data 7 notice and without obligation of DoorKing, Inc. to notify any persons of any such revisions or changes. Monitored Gate Tracker Busy 8 External Connection Not Used 9...
  • Page 5: Table Of Contents

    5.2 Diagnostics Check 28-29 5.3 Troubleshooting 29-30 5.4 Accessories 1175 Wiring Schematic SECTION 6 - OWNER OF THE GATE/DOOR OPERATOR 8.1 Alarm Sounding and Gate/Door WILL NOT Operate 8.2 Manual Gate/Door Operation 8.3 Gate/Door Operators Monthly Checkup Printable Safety Page...
  • Page 6: Overhead Gate/Door Protection

    Note: Make sure the gate/door opens and closes smoothly. Gate/door should stay In the r e d open position when springs are n i t o n s o properly balanced before o t o operator installation. 1175-065-H-8-18...
  • Page 7: Gate/Door Construction

    2. A warning placard shall be placed adjacent to the controls. 3. An automatic closing device (such as a timer, loop sensor, or similar device) shall not be employed. 4. No other activation device shall be connected. Continued on next page. 1175-065-H-8-18...
  • Page 8: Important Notices

    Do not allow children to play in the area of the operator or to play with any gate/door-operating device. • To remove the gate/door operator from service, operate the gate/door to the full open position and then shut off power to the operator at the service panel. 1175-065-H-8-18...
  • Page 9: Ul325 Entrapment Protection

    Type C - Inherent force limiting, inherent adjustable clutch or inherent pressure relief device. Type D - Actuating device requiring constant pressure to maintain opening or closing motion of the gate/door. * B1 and B2 means of entrapment protection must be MONITORED. 1175-065-H-8-18...
  • Page 10: Glossary

    ENTRAPMENT - The condition when an object is caught or held in a position that increases the risk of injury. 1175-065-H-8-18...
  • Page 11: Section 1 - Installation

    Gate/door should REMAIN in the open position when balancing springs are properly adjusted. IF the operator is installed less than 8 feet above the floor, then operator’s exposed moving parts must be covered. DoorKing offers a 1175 cover for protection, Sold separately, P/N 1175-020 Ceiling...
  • Page 12: Manual Release And Chain Connection

    Do not let chain touch steel rail separators. Approximate chain tension, front rail removed for illustration. Chain must be centered between rails. Return wheel must be centered between rails. Chain tension adjustment. Adjust equally on both sides of rails. 1175-065-H-8-18...
  • Page 13: Attach Gate/Door Bracket

    B r a B r a i n e i n e n t e n t e Install the header bracket with lag bolts or anchor sleeves. Bracket must be mounted level! 1175-065-H-8-18...
  • Page 14: Mount Operator

    Rails must be mounted level! Mount Powerhead Using a Ceiling Extension Bracket Ceiling Ceiling extension bracket must be fabricated (2” wide L angle steel is recommended). Install the powerhead with lag bolts or anchor sleeves. Rails must be mounted level! 1175-065-H-8-18...
  • Page 15 Permanently install the supplied warning signs in locations so that the signs are visible by persons on both sides of the gate/door. • Use appropriate hardware such as wood or sheet metal screws (not supplied) to install the warning signs. 1175-065-H-8-18...
  • Page 16: External Entrapment Protection Installation

    Junction Avoid interference with gate/door hardware. CLOSING Reversing Edge: Obstructed close-direction reversing edge will Typical Reversing Edge Reverse the gate/door back to the mounted on bottom of gate/door. open position. Another input is needed to close the gate/door. 1175-065-H-8-18...
  • Page 17: 3-Button Control Station Installation

    See page 17 to wiring control station to gate/door operator. Type of wiring to be used on ALL external devices: A) Type CL2, CL2P, CL2R, or CL2X. B) Other cable with equivalent or better electrical, mechanical, and flammability ratings. 1175-065-H-8-18...
  • Page 18: Section 2 - Wiring

    Use only sweeps for conduit bends. Do not use 90° connectors as this will make wire pulls very difficult and can cause damage to wire insulation. Sweep • We suggest that minimum ¾-inch conduit be used. Elbow • Be sure that all conduits are installed in accordance with local codes. 1175-065-H-8-18...
  • Page 19: High Voltage Wire Run

    12 AWG 10 AWG 8 AWG 6 AWG 1175 Never run high voltage and low voltage wires in the same conduit. Keep them in separate conduits. 2.3 High Voltage Terminal Connection High Voltage DO NOT cycle the operator without the OPEN and CLOSE limit nuts in their specific open and close positions.
  • Page 20: Main Terminal Description

    Close LED Close N.O. floor and at least 6 ft from gate/door. Stop LED Stop N.C. See page 13 for info about installation. (DoorKing’s 3-wire 3-button control Common station cannot be used) 3-Pin with • When using a 3-button control •...
  • Page 21: Control Wiring

    20-Pin Main source. interruptions, etc. For more detailed information refer to the Tracker Terminal Installation and Wiring Manual, DoorKing P/N 2358-065. 1175-065-H-8-18...
  • Page 22: External Entrapment Protection Wiring

    ON for each Avoid interference with gate/door hardware. Close Edge connected device. 2 3 4 Monitored Device Note: Only 1 monitored Device can be connected to each input. An OPTIONAL Expansion Board (sold separately) will allow connection for additional devices. 1175-065-H-8-18...
  • Page 23: Loop Detector Wiring

    Loop detectors must be installed to prevent the gate/door from accidentally closing on vehicles that may be in the path of the gate/door. • Install 9410 Single Channel or 9409 Dual Channel DoorKing plug-in loop detectors (Sold separately). • If using external loop detectors, use only UL listed (or equivalent) detectors. Use a separate power supply for external loop detectors.
  • Page 24: Section 3 - Adjustments

    Reverse Sensor Plug Not used the relay shorting bar on the N.O. or Chassis N.C. pins respectively. Adjust reversing sensitivity for the open AND close direction of Ground the operator. Secondary adjustment is NOT used. See page 23. Secondary Primary 1175-065-H-8-18...
  • Page 25: Dip-Switch Descriptions And Functions

    Magnetic lock Magnetic lock is used and connected to terminals 9 and 13. See page 17 for wiring. Switch 3 MUST be in ON Position. Switch 4 MUST be turned OFF for Model 1175 operator. Leave in OFF position. Switch 1 Switch 2 If a magnetic lock is not used with the gate/door operator, leave this switch in the OFF position.
  • Page 26: Limit Sensor Adjustments

    Open Limit Close Limit Push and Hold Tab EXIT LOOP Close Limit LED Open Limit LED 1477-010 2 3 4 POWER TIME DELAY REV SENSE REV SENSE SECONDARY PRIMARY REVERSE LOOP 4405-018 Power Switch Alarm Alarm Reset 1175-065-H-8-18...
  • Page 27: Inherent Reverse Sensor Adjustment

    PRIMARY gate/door strikes it while closing. Gate/door must REVERSE direction REVERSE LOOP and open! Re-adjust Close sensor if necessary. Note: If alarm sounds while performing these tests, press alarm reset button to shut off alarm. 4405-018 Alarm Alarm Reset 1175-065-H-8-18...
  • Page 28: Section 4 - Operating Instructions

    4.1 Power Switch and Alarm Reset Switch AC Power Switch - Powers the operator ON (toggle up) or OFF (toggle down). Alarm Siren Alarm Reset Switch - Used to turn off the entrapment alarm and to reset the operator after a hard shutdown has occurred. 1175-065-H-8-18...
  • Page 29: Shutdown Conditions

    After 5 minutes, the audio alarm will “chirp” every 5 seconds. This indicates that the operator is in a hard shutdown condition and the reset switch must be activated to reset the operator and silence the alarm. Continued on the next page 1175-065-H-8-18...
  • Page 30: Manual Gate/Door Operations

    Inspect the gate/door and gate/door hardware. NOTE: DoorKing operators have a built-in alarm reset push button mounted on the operator above the power ON-OFF toggle switch. Activating this button will return the gate/door operator to normal operation, but will not activate the gate/door operator.
  • Page 31 M A s s L i n a i n t c h r r i a a i n IMPORTANT: The carriage assembly’s spring loaded chain catch will ONLY lock into place in the DOUBLE MASTER CHAIN LINK. 1175-065-H-8-18...
  • Page 32: Section 5 - Technical Instructions

    Check the input indicator LEDs. They should only come ON when an external keying device (card reader, push button, etc.) is activated. If any of the input LEDs are ON continuously, the gate/door will not operate. Disconnect the external keying devices one at a time until the LED goes OFF. 1175-065-H-8-18...
  • Page 33: Troubleshooting

    Pull the loop detector circuit boards from the loop ports on the operator circuit board. If the malfunction persists, the problem is not with the loop system. For more information refer to the loop detector instruction sheet and the DoorKing Loop and Loop Detector Information Manual.
  • Page 34 Replace with a known good detector and re-check. If problem continues, control board may be bad. reverse gate/door. • If loop detector LED does not illuminate, see above symptom. Operator has intermittent • The main terminal #3 250 mA power has been exceeded. Check total amp draw of connected device(s). functionality problems that vary. 1175-065-H-8-18...
  • Page 35: Accessories

    5.4 Accessories UL 325 Monitored Entrapment Protection Devices available for the model 1175 commercial overhead gate/door operator. Type B2 Contact Sensors (Reversing Edge) Miller Edge Sensing Edges - all models with a T2 (resistive) termination. Miller Edge wireless monitored transmitter/receiver kit model RB-G-K10...
  • Page 36: 1175 Wiring Schematic

    1175 Wiring Schematic Orange Yellow PUSH TO OPERATE technician use only Brown EXIT LOOP 1477-010 2 3 4 POWER TIME DELAY REV SENSE REV SENSE SECONDARY PRIMARY White REVERSE LOOP Yellow 1/2 HP Single Phase Blue 4405-018 Ground Neutral Chassis Ground...
  • Page 37: Section 6 - Owner Of The Gate/Door Operator

    The audio alarm will sound for five minutes, or until the operator’s reset button is pushed. After (5) five minutes the alarm will “chirp every 5 sec.” and the hard shutdown condition will remain in affect until the reset button is pushed. Please read SECTION 4 - OPERATING INSTRUCTIONS for more information about operating this gate/door operator. 1175-065-H-8-18...
  • Page 38: Manual Gate/Door Operation

    IMPORTANT: The carriage assembly’s spring loaded chain catch will ONLY lock into place in the DOUBLE MASTER CHAIN LINK. Please read SECTION 4 - OPERATING INSTRUCTIONS for more information about operating this gate/door operator. 1175-065-H-8-18...
  • Page 39: Gate/Door Operators Monthly Checkup

    If you feel uncomfortable performing any of these inspections or testing, a qualified service technician will perform the visual inspections and testing for you. You can find a trained service technician at DoorKing’s “Dealer Locator” at www.doorking.com Visual Inspection Visually inspect the rollers, fasteners, brackets, chain and other gate/door hardware for proper alignment, proper tightness, and signs of damage, breakage, looseness, rust or wear.
  • Page 40 1175-065-H-8-18...
  • Page 41 1175-065-H-8-18...
  • Page 42 Installation/Owner’s Manual Model 1175 Model 1175 Model 1175 Commercial Overhead Gate/Door Operator Use this manual for circuit board 4405-018 Revision A or higher. 1175-065-H-8-18 UL 325 August 2018 Standard EXTERNAL ENTRAPMENT PROTECTION MUST be installed or the gate/door operator WILL NOT function.

Table of Contents