Chapter 6 Parameter Setup
6.5 Network Variable Registration/Assignment
Assign the FL-net common memory to system network variable. This enables the S
controller user program to use the cyclic data in common area 1 and 2 communicated by
FL-net cyclic transmission as network variables. The S controller OS batch transfers the
data between the FL-net common memory area and network variable at the beginning of
sequence.
6.5.1 Transmission Block Registration
Register the area in common memory transmitted by each FL-net module as transmission
block.
(1)
6
(2)
22
Select the network folder FL-netLAN, select [Scan Memory] at the bottom right of the
screen, and then select <File (F)><Transmission Block> to open the Edit
Transmission Block screen.
Register the area in common memory transmitted by FL312 of FL312TST_1 and
FL312TST_2.
Note1: Leave [Transmission Speed] set to [Middle] for FL-netLAN.
Note2: In Engineering Tool, the start address of area 2 is assumed to be 512.
Figure 6-8 Registering FL-netLAN transmission blocks
model 3000 FA Control Network [FL-net(OPCN-2)] FL311/FL312 Module Operation Manual