Parameter Setup - Toshiba V Series Operation Manual

Integrated controller, control network fl-net opcn-2, module
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

Chapter 6 Parameter Setup

6.3 Parameter Setup

The FL312 parameters are set as follows:
(1)
(2)
(3)
Table 6-1 shows the FL312 parameter setup items and Figure 6-4 shows a setup screen
example.
6
Setup item
Cyclic transmission
Message transmission
IP address selection
IP address
Token monitor time
Minimum permission
frame interval
Talker top address 1
Talker word size 1
Talker top address 2
Talker word size 2
Own node name
Note1: FL-net default is 192.168.250.*
18
Select FL312TST_1 - FL312 from the product tree and select <File (F)><Module
parameter>.
The parameter setup screen titled "Module Parameters" appears. The FL312
parameters are set on this screen.
Set the parameters for FL312 of FL312TST_2 in the same manner.
Table 6-1 FL312 parameter setup items
Allow or prohibit cyclic transmission.
Yes means "Enable", No means "Disable".
Normally select "Yes".
Allow or prohibit message transmission.
Normally select "Yes".
Select whether to set the FL312 IP address with hardware
switches on the module or use the value set with Engineering
Tool 2.
Set the FL312 IP address when IP address selection is set to
Tool.
Allowed range: 192.168.250.1 to 192.168.250.254
Note: If IP address selection is set to Hardware, this parameter
is ignored.
Set in 1 ms unit.(Range is 1 to 255 ... 1 to 255 ms)
Set in 0.1 ms unit.(Range is 0 to 50 ... 0 to 5 ms)
Specify the own node transmission area start address of the bit
data area in FL-net common memory. (Word address)
Bit data area is 8 k bits (=0.5 k word)
Own node transmission size of bit data area. Set in word unit.
Specify the own node transmission area start address of the
word data area in FL-net common memory. (Word address)
Word data area is 8 k words
Own node transmission size of word data area.
Set in word unit.
Enter the name (facility name) of FL312.
*: Node address switch value which is set to 01 at factory shipment.
model 3000 FA Control Network [FL-net(OPCN-2)] FL311/FL312 Module Operation Manual
Description
Default
Yes
(allow transmission)
Yes
(allow transmission)
Hard
(module switch
setting) (Note 1)
0.0.0.0
50
2
0
Note: Start of area 1 is
set to "0" by the
Engineering Tool.
0
512
Note: Start of area 2 is
set to "512" by the
Engineering Tool.
0
TargetNode

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3000 faFl311Fl312

Table of Contents