Chapter 10 FL312 Dedicated Requests
(6)
(7)
10
Control information detail
STBY
RUN
MTEN
CTEN
42
Own node parameter set request
Request to set parameter in FL312 after initializing with reset request.
Parameters are downloaded form Engineering Tool.
This request is accepted only when FL312 is in standby mode. After parameter is set,
FL312 mode must be changed to online mode with control request.
CMD
F
+0
6
Note1: The completion status (see appendix) of this request is stored in STATUS of
XMIT_T.
Figure 10-6 Own node parameter set request
Operation mode control request
Request to control the FL312 operation mode from S controller.
CMD
F
+0
7
Control information
F
E
D
C
B
RUN
STBY
Bit name
1: Change from RUN mode to standby mode
1: Change from standby mode to RUN mode
When RUN=1, specify whether to allow or prohibit message transmission.
0: Prohibit message transmission
1: Allow message transmission
When RUN=1, specify whether to allow or prohibit cyclic transmission.
0: Prohibit cyclic transmission
1: Allow cyclic transmission
Note1: The completion status (see appendix) of this request is stored in STATUS of
XMIT_T.
The following specifications are prohibited. (Error completion status is
returned.)
・ Simultaneous issuing of standby request and RUN request
・ Specification of already entered mode
・ Issuing this request during down mode
Check the node status to determine that the mode has actually changed.
If RUN request is issued with no parameter set, error completion status is
returned.
Figure 10-7 Operation Mode control requests
0
0
A
9
8
7
6
Description
model 3000 FA Control Network [FL-net(OPCN-2)] FL311/FL312 Module Operation Manual