Chapter 8 Cyclic Transmission・・・・・・・・・・・・・・27; Data Transfer By Batch I - Toshiba V Series Operation Manual

Integrated controller, control network fl-net opcn-2, module
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

This chapter describes the handling of data communicated with other nodes through cyclic
transmission. Cyclic data is communicated through FL312 common memory.
8.1 Data Transfer by Batch I/O
Data I/O by batch I/O is the most common data transfer method for the S controller. This is
the method used to perform "Network Variable Registration/Assignment" with Engineering
Tool 2 as described in section 6.5. With this assignment, the data in common memory is
assigned to network variables and the data transfer between the common memory and the
network variable is performed by the S controller OS in batch at the beginning of the
sequence. Therefore, the user program can treat data as network variables without being
aware of the common memory.
FL312 common memory
Area 1
512 words
Area 2
8k words
The data type is WORD or BOOLEAN with this method. Therefore, data synchronicity is
guaranteed only up to one word (16 bits). If synchronicity of multiple word data is necessary,
refer to the following section "Data Transfer by I/O Instruction."
6F8C1067
Chapter 8 Cyclic
Transmission
Set with
engineering tool
Figure 8-1 Common memory and network variable assignment
S controller network variable
FL-net
area
27

Hide quick links:

Advertisement