Advertisement

5. Data Report

The device will immediately send a version packet report along with an uplink packet including battery voltage and pulse
count.
The device sends data in the default configuration before any configuration is done.
Default Setting:
MaxTime: Max Interval = 60 min =3600s
MinTime: Max Interval = 60min = 3600s
BatteryChange = 0x01 (0.1v)
FilterTime = 0x02 (10ms)
Pulse Counter Clear Mode:
Pulse Counter has two mode to option
a. Clear When SEND:0x00 (default)
Clear the pulse count after reporting data packet
b. Clear When Roll-Over:0x01 (Enable the mode by command ConfigureCmd)
Accumulate each pulse count, it will clear pulse count reach 0xFFFF then report an uplink packet (0xFFFF), and restart
count. (When device reset or reboot, it will clear pulse count data, too)
Note:
(1) The input pulse width is greater than 100ms to accurately count
(2) The device report interval will be programmed based on the default firmware which may vary.
(3) The interval between two reports must be the minimum time
Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver
http://www.netvox.com.cn:8888/page/index
Data report configuration and sending period are as following:
Min Interval
(Unit:second)
Any number between
1~65535
to resolve uplink data.
Max Interval
(Unit:second)
Any number between
1~65535
Reportable Change
Can not be 0.
5
Current Change≥
Reportable Change
Report
per Min Interval
Current Change<
Reportable Change
Report
per Max Interval