Page 1
This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX Technology. The...
Table of Content 1. Introduction ........................................2 2. Appearance ........................................2 3. Main Features ....................................... 3 4. Set up Instruction ......................................3 5. Data Report ........................................5 6. Filtering time ........................................ 9 7. Installation ........................................10 8. Information about Battery Passivation ............................... 11 8.1 To determine whether a battery requires activation ...........................
1. Introduction R718H2 is the wireless 2-Input Pulse Counter Interface of Netvox ClassA type device based on LoRaWAN open protocol that is compatible with LoRaWAN protocol. LoRa Wireless Technology: LoRa is a wireless communication technology famous for its long-distance transmission and low power consumption. Compared with other communication methods, LoRa spread spectrum modulation technique greatly extend the communication distance.
Low power consumption and long battery life Battery Life: ⁻ Please refer to web: http://www.netvox.com.tw/electric/electric_calc.html ⁻ At this website, users can find battery life time for variety models at different configurations. 1. Actual range may vary depending on environment.
Page 5
Network Joining Turn on the device to search the network. Never join the network The green indicator stays on for 5 seconds: success The green indicator remains off: fail Turn on the device to search the previous network. Had joined the network The green indicator stays on for 5 seconds: success (Not restore to the factory setting) The green indicator remains off: fail...
(2) The device report interval will be programmed based on the default firmware which may vary. (3) The interval between two reports must be the minimum time Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver http://www.netvox.com.cn:8888/page/index to resolve uplink data.
Page 7
DeviceType ReportType NetvoxPayLoadData Version– 1 byte – 0x01—— the Version of Netvox LoRaWAN Application Command Version DeviceType– 1 byte – Device Type of Device The devicetype is listed in Netvox LoRaWAN Application Devicetype doc ReportType – 1 byte – the presentation of the NetvoxPayLoadData,according the devicetype NetvoxPayLoadData–...
Page 9
(6) Read the Pulse Counter Clear Mode Configuration: Downlink: 063F000000000000000000 Response: 863F010000000000000000 (Current device parameter) Example for MinTime/MaxTime logic: Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V MaxTime MaxTime Sleeping(MinTime) Sleeping(MinTime) Wake up and collects data Wakes up and collects data Wakes up and collects data REPORTS 3.6V...
1) The device only wakes up and performs data sampling according to MinTime Interval. When it is sleeping, it does not collect data. 2) The data collected is compared with the last data reported. If the data variation is greater than the ReportableChange value, the device reports according to MinTime interval.
7. Installation 1. Wireless 2-Input Pulse Counter Interface (R718H2) has the 2. Wireless 2-Input Pulse Counter Interface (R718H2) is built-in magnet (as the figure below). When installed, it can be sent according to the maximum and minimum interval, and attached to the surface of an object with iron which is convenient the count is automatically cleared after transmission and quick.
8. Information about Battery Passivation Many of Netvox devices are powered by 3.6V ER14505 Li-SOCl2 (lithium-thionyl chloride) batteries that offer many advantages including low self-discharge rate and high energy density. However, primary lithium batteries like Li-SOCl2 batteries will form a passivation layer as a reaction between the lithium anode and thionyl chloride if they are in storage for a long time or if the storage temperature is too high.
9. Important Maintenance Instruction Kindly pay attention to the following in order to achieve the best maintenance of the product: • Keep the equipment dry. Rain, moisture and various liquids or water may contain minerals that can corrode electronic circuits. In case the device is wet, please dry it completely. •...