Ups Settings - Njoy Balder Series User Manual

Ups unit
Hide thumbs Also See for Balder Series:
Table of Contents

Advertisement

Available languages

Available languages

5.5

UPS Settings

Parameter 1
88
Vac
8 8 8 8 8 8
Parameter 2
Parameter 3
There are three parameters to set up the UPS. Refer to fol-
lowing diagram.
Parameter 1:
For program alternatives. There are 16 pro-
grams to set up. Refer to the table below.
Parameter 2 and 3:
The settings options or values for each
program.
NOTE:
Most of Balder UPS parameters can be set-up only
on Bypass mode (see below table); please be sure you are in
Bypass mode and then press and hold Test/Up + Mute/Down
Buttons simultaneous more than 1s to enter the setting menu
(see section 5.1 for details).
Programs available list for parameter 1:
Bypass/
Description
Code
No
AC ECO CVCF Battery
output
Output
01
Y
voltage
Output
02
Y
frequency
Voltage range
03
Y
for bypass
Frequency
range for
04
Y
bypass
26
Vac
Battery
Test
Bypass/
Description
Code
No
AC ECO CVCF Battery
output
ECO mode
enable/
05
Y
disable
Voltage range
06
Y
for ECO mode
ECO mode
frequency
07
Y
range setting
Bypass mode
08
Y
Y
setting
Battery backup
09
Y
Y
time setting
Reserved
10
Reserved
11
Hot standby
function
12
Y
Y
enable/disable
Battery
voltage
13
Y
Y
adjustment
Charger
voltage
14
Y
Y
adjustment
Inverter
voltage
15
Y
adjustment
Output
voltage
16
Y
calibration
*Y means that this program can be set in this mode.
NOTE:
All parameter settings will be saved only when UPS
shuts down normally. Normal UPS shutdown means turning off
input breaker in bypass mode.
Battery
Test
Y
Y
Y
Y
Reserved for future use
Reserved for future use
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y