2.3. Single UPS installation

Installation and wiring must be carried out in accordance with the local
electric laws and regulations by trained professionals.
Step 1.
Make sure that the mains wire and breakers of the building are
rated for the capacity of the UPS to prevent electric shock or risk of fire.
NOTE!
Do not use the wall receptacle as the input power source for the UPS, as its rated
current is less than the UPS's maximum input current. The receptacle may be
damaged and destroyed.
Step 2.
Switch off the mains switch in the building before installation.
Step 3.
Turn off all the connected devices before connecting to the UPS.
Step 4.
Prepare wires based on the following table:
Model
Input (Ph)
Garun 10KL
14
HV 15K
12
Garun 30KL
8
Garun 40KL
6
Garun 60KL
4
Garun 80KL
2
• The cable for Garun 10KL should be able to withstand over 20A current.
It is recommended to use AWG 14 or thicker wire for Phase and AWG10 or
thicker wire for Neutral for safety and efficiency.
• The cable for Garun 15KL should be able to withstand over 30A current.
It is recommended to use AWG 12 or thicker wire for Phase and AWG10 or
thicker wire for Neutral for safety and efficiency.
• The cable for Garun 20KL should be able to withstand over 40A current.
It is recommended to use AWG10 or thicker wire for Phase and AWG 6 or
thicker wire for Neutral for safety and efficiency.
• The cable for Garun 30KL should be able to withstand over 60A current.
It is recommended to use AWG 8 or thicker wire for Phase and AWG 4 or
thicker wire for Neutral for safety and efficiency.
• The cable for Garun 40KL should be able to withstand over 80A current.
It is recommended to use AWG 6 or thicker wire for Phase and AWG 4 or
thicker wire for Neutral for safety and efficiency.
12
Wiring spec (AWG)
Output (Ph)
Neutral
Battery
Ground
14
10
8
8
12
10
-
8
8
4
4
4
6
4
4
4
4
1
1
4
2
1/0
1/0
2
• The cable for Garun 60KL should be able to withstand over 120A current.
It is recommended to use AWG 4 or thicker wire for Phase and AWG 1 or
thicker wire for Neutral for safety and efficiency.
• The cable for Garun 80KL should be able to withstand over 160A current.
It is recommended to use AWG 2 or thicker wire for Phase and AWG 1/0 or
thicker wire for Neutral for safety and efficiency.
• The selections for color of wires should be followed by the local electrical
laws and regulations.
Step 5.
Remove the terminal block cover at the rear panel of UPS.
Then connect the wires according to the following terminal block diagrams:
(Connect the grounding/earthing wire first when making wire connections.
Disconnect the earth wire after you disconnect the power wire.)
Terminal block wiring diagram for Garun 10KL, 15KL, 20KL
Terminal block wiring diagram for Garun 30KL, 40KL