Lcd Display Wordings Index; Ups Settings - Njoy Balder Series User Manual

Hide thumbs Also See for Balder Series:
Table of Contents

Advertisement

Available languages

Available languages

6.4. LCD display wordings index

Abbreviation
Display content
E N A
ENA
d 1 5
DIS
A O
ATO
b A
BAT
N C F
NCF
C F
CF
S U b
SUB
A d d
ADD
O N
ON
O F F
OFF
F b d
FBD
O P N
OPN
E S
RES
O P. U
OP.V
P A
PAR
18
Meaning
Enable
Disable
Auto
Battery
Normal mode (not CVCF
mode)
CVCF mode
Subtract
Add
On
Off
Not allowed
Allow
Reserved
Output voltage
Parallel

6.5. UPS settings

Parameter 1
88
Vac
8 8 8 8 8 8
Parameter 2
There are three parameters to set up the UPS. Refer to following diagram.
• Parameter 1: For program alternatives. There are 16 programs to set up.
Refer to the table below.
• Parameter 2 and 3: The settings options or values for each program.
NOTE!
Most of Balder UPS parameters can be set-up only on Bypass mode (see below
table); please be sure you are in Bypass mode and then press and hold Test/Up +
Mute/Down Buttons simultaneous more than 1s to enter the setting menu (see
section 5.1 for details).
Programs available list for parameter 1:
By-
pass/
Description
Code
No
output
Output voltage
01
Y
Output frequency
02
Y
Voltage range for
03
Y
bypass
Frequency range
04
Y
for bypass
ECO mode
05
Y
enable/ disable
Vac
Parameter 3
Battery
AC
ECO
CVCF Battery
Test
19