5.3.6.7

View Voltages

Press '7' to select the View Voltages option. The display initially shows the voltage across the battery.
For example:
Press the
viewed and their normal values). For example:
Press 'X' to return to the View menu.
Signal
BATTERY VOLTS
CHARGER
AC POWER
BATTERY WIRING
MONITORED INPUT 2
MONITORED INPUT 1
SOUNDER 2
SOUNDER 1
EARTH
Measurement readings shown are for indicative purposes only.
1
The measurement reading depends also on battery capacity and condition.
5.3.6.8

View Version

Press '8' to select the View Versions option. The display shows the part number and version of the
software installed in the panel. It also shows the loop driver protocol and software version loaded into
the signalling loop driver circuit. For example:
Press 'X' to return to the View menu.
Page 36
[U0 VOLTS]
and
keys to view other readings (see table below for full list of signals that can be
[U0 VOLTS]
Description
Measurement of the Battery Voltage
Measurement of the Charger Output Voltage
Measurement of the AC Power Input
Measurement of the battery wiring resistance
Measurement of the input signal condition
Measurement of the input signal condition
Measurement of the output wiring condition
Measurement of the output wiring condition
Measurement of the earth condition
Table 7 – Voltage / Analogue Value Readings
[U0 VERSION] System : 993-667-000
Loop
Document No. 996-148-000-5, Revision: 5
BATTERY VOLTS = 23.6
:Select
X:Exit
CHARGER = 26.5
:Select
X:Exit
: Apollo
Dimension Series
Value
Normal
Reading /
Range
Volts
24 (19-28)
Volts
27 (20-29)
Volts
240 (190-260)
1
mOhms
350 (200-500)
Count
500 (480-520)
Count
500 (480-520)
Count
190 (170-210)
Count
190 (170-210)
Count
270 (240-300)
3.00