Dimension Series
5.3.6.1.2

Apollo Device Information

[L1 Sensor 001] Type OPT
DISCOV
The display shows the following information:
Device Type:
OPT
Level:
023
Family:
DISCOV (S90, XP95, DISCOVERY)
Input Bits:
LLL
Output Bits:
LLL
Drift:
00
Mode:
03
For further information refer to manufacturers data sheets.
5.3.6.1.3

Hochiki Device Information

[L1 Sensor 001] Type OPT
S:096
The display shows the following information:
Device Type:
OPT
Level:
023
S:
096
ZP:
061
FP:
188
Mode:
--
For further information refer to manufacturers data sheets.
5.3.6.1.3.1 Hochiki Multi Input/ Output devices
For Hochiki devices with multiple digital inputs and/or outputs, the status of each individual input and
output is shown. The example below shows how the current status of the 1 input and 2 outputs of a
CHQ-B module might be displayed. In the example, the 'L' symbol associated with the input indicates
a Logic Low (inactive) condition, the 'H' symbol is associated with output 'a' (Logic High / Active state)
and the 'L' indicates a Logic Low/ inactive output 'b' condition.
[L1 Sensor 001] Type I/O
User Manual
Input(2-0):LLL Drift:+00 Mode:03
For a list of the device type abbreviations refer to Table 4 – Device Type
Abbreviations.
(Analogue Value - For sensors; default pre-alarm level is 45, default fire alarm
level is 55. For modules; fault level is 4, normal level is 16 and input activated
level is 64)
(Digital Input Status for input bits 0-2, H=Logic High, L=Logic Low)
Not shown in example, used for multiple output I/O modules only (Digital Output
Status of individual device outputs, H=Logic High, L=Logic Low)
(Shows the amount of drift compensation employed by the device, range ±16, –
Discovery Only)
(Shows the operating mode of the device, range 1-5, – Discovery Only)
ZP:061
FP:188
For a list of the device type abbreviations refer to Table 4 – Device Type
Abbreviations.
(Analogue Value - This is a normalised number to account for offsets, calibration
and differences in device type. For sensors; default pre-alarm level is 45, default
fire alarm level is 55. For modules; fault level is 4, normal level is 16 and input
activated level is 64).
(Unprocessed raw analogue value returned by the device)
(Zero Point Value when the device was last calibrated)
(Fire Point Value when the device was last calibrated)
(Current detection mode enabled in the multi-sensor or multi-mode heat detector)
Inputs(1-1): L
Document No.996-148-000-5, Revision: 5
Level 023
Level 023
Mode:--
Level 000
Outputs(a-b): HL
MORLEY-IAS
Page 33