UPS5000-S-(40 kVA-200 kVA)
User Manual (IP42, 40 kVA Power Modules)
Step 4 Connect signal cables to each UPS.
----End
3.9 Installation Verification
Table 3-5
If the check results of listed items 8 and 9 in
UPS may be damaged.
Table 3-5 Installation checklist
Issue 03 (2020-01-10)
Figure 3-38 Signal cable connections in a dual-bus parallel system
lists check items.
No.
Item
01
UPS installation
02
Neat arrangement
03
Cable layout
04
Cable labels
Copyright © Huawei Technologies Co., Ltd.
Table 3-5
do not meet the acceptance criteria, the
Acceptance Criteria
The UPS is securely installed and does not tilt
due to vibration.
The UPS and its adjacent cabinets are neatly
arranged and secured with connecting plates.
Cables are routed properly and cable routing
meets customer requirements.
Both ends of a cable are labeled. Labels are
3 Installation