Huawei UPS5000-S Series User Manual page 106

Ip42, 40 kva power modules
Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(40 kVA-200 kVA)
User Manual (IP42, 40 kVA Power Modules)
Input Settings
Figure 4-21 Input settings
Issue 03 (2020-01-10)
Item
Description
D.G. mode
Set this parameter to Enable
when a D.G. connects to the
input PDC. The UPS enters the
D.G. mode when a D.G. is
detected over dry contacts.
D.G. power
Set these two parameters to
limiting (kVA)
control the valid input current
and limiting input current, which
D.G. charger
prevents load impact and
power ratio (%)
facilitates better cooperation
between the UPS and the D.G.
Input cur.
Specifies whether to enable or
limiting
disable input current limiting to
protect generators.
Input cur.
Limits the input current to protect
limiting ratio
the D.G.
(%)
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable, Enable
Depends on the
0 kVA to 5000
actual model.
kVA
0
0%–100%
Disable
Disable, Enable
200%
50%–200%
98