Power Distribution Module; Monitoring System; Overview - Huawei UPS5000-S Series User Manual

Ip42, 40 kva power modules
Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(40 kVA-200 kVA)
User Manual (IP42, 40 kVA Power Modules)

2.3.5 Power Distribution Module

Figure 2-13 Power distribution module
Functions
Specifications
The power distribution module provides a loading capability of 200 kVA.

2.3.6 Monitoring System

2.3.6.1 Overview

The monitoring system consists of a CM and MDU, as described in
Issue 03 (2020-01-10)
(1) Battery input terminals
(4) Output terminals
The power distribution module provides mains and bypass three-phase, four-wire input
terminals and PE on the UPS rack, provides three-phase, four-wire output terminals for
the whole system, and provides battery string input terminals.
By using the maintenance bypass switch, the power module and bypass module inside
the cabinet can be maintained without disconnecting power supply.
You can short-circuit the mains and bypass input terminals using copper bars, so that two
mains inputs merge into one mains input.
Copyright © Huawei Technologies Co., Ltd.
(2) Bypass input terminals
(5) Maintenance bypass
switch
2 Overview
(3) Mains input terminals
Table
2-4.
26