UPS5000-S-(40 kVA-200 kVA)
User Manual (IP42, 40 kVA Power Modules)
Alarm ID
Alarm Name Severity
(Alarm ID-
Cause ID)
0043-1
Fan abnormal
0043-2
0043-3
0043-4
0047-1
Not ready
0060-4
Inverter
abnormal
0061-2
Inverter alarm
0061-7
Inverter alarm
Issue 03 (2020-01-10)
Cause
Critical
The fan for
the power
module is
abnormal.
The fan
monitoring
cable for the
power
module is not
working
properly.
The fan is
faulty.
The fan is
faulty.
The fan
monitoring
cable is
faulty.
Critical
The ready
switch is OFF.
Critical
A load short-
circuit
occurs.
A short
circuit occurs
inside the
module.
(This fault
seldom
occurs.)
The output is
incorrectly
grounded.
Minor
The I2C bus
is not
normal.
The
E2PROM is
faulty.
Minor
The bypass
waveform is not
normal.
Copyright © Huawei Technologies Co., Ltd.
Solution
Replace the faulty power module.
Check the fan or replace the bypass
module.
1. Replace the fan.
2. Check the fan monitoring cable.
Close the ready switch.
1. Check load cable distributions.
2. Check whether the output is grounded.
3. If the load cable connections are
normal and the output is correctly
grounded, replace the power unit or
module.
1. Rectify the fault and check whether the
alarm is cleared.
2. If the alarm is generated again, replace
the power module.
If not all modules generate the alarm,
start the UPS, transfer it to normal
mode, and replace the faulty module.
If all modules generate the alarm, open
B Alarm List
189