UPS5000-S-(40 kVA-200 kVA)
User Manual (IP42, 40 kVA Power Modules)
Input Settings
Output Settings
Issue 03 (2020-01-10)
Item
Description
is set to Enable, the control chip
RAM working status is checked
regularly. If this parameter is set
to Disable, regular check is
disabled.
Record time
Indicates the time for storing
after fault
fault data after the UPS
experiences a fault. The default
value is 0 ms, which means that
the data during 20 ms before the
fault occurs is recorded. If the
value is set to 40 ms, it means
that the data during 20 ms before
the fault occurs and the data
during 40 ms after the fault
occurs are recorded, and the like.
Collect real-
If this parameter is set to Enable,
time site
one waveform can be stored
waveform
manually.
BCB trips in
If this parameter is set to Enable,
case of EOD
the BCB will trip in case of
EOD.
Item
Description
Input
The value of Input adaptability
adaptability
can be Strong or Weak. Strong
input adaptability applies to the
D.G. or input sources whose
input current has high frequency
oscillation. In this mode, the total
distortion of the input current
waveform (THDi) is poor, but
the system is stable. Weak input
adaptability is suitable for mains
and AC input sources.
Item
Description
Zero display
If this parameter is set to Enable,
with no load
the output current is displayed as
output
0 when no load is output. The
output load rate is displayed as
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
0 ms
0 ms, 20 ms, 40
ms, 60 ms, 80
ms
Disable
Disable, Enable
Enable
Disable, Enable
Default Value
Value Range
Strong
Strong, Weak
Default Value
Value Range
Enable
Disable, Enable
119