Huawei UPS5000-S Series User Manual page 109

Ip42, 40 kva power modules
Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(40 kVA-200 kVA)
User Manual (IP42, 40 kVA Power Modules)
Battery Settings
Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge
time. When you set battery parameters, note the following:
Figure 4-24 Battery settings 1
Issue 03 (2020-01-10)
Item
Description
frequency
bypass input frequency and the
range (Hz)
rated frequency is greater than
the specified value, the system
determines that the bypass
frequency is abnormal, so the
bypass is unavailable. The
frequency range must be greater
than the ECO frequency range.
Battery string sharing is unavailable when Single/Parallel is set as Single.
Battery string sharing affects the actual charge current and the estimated discharge time.
An incorrect setting will cause a high or low charge current, which may damage the
batteries. An incorrect estimated discharge time may cause a data backup fault.
When you set parameters, ensure the following: Dis. cur. 0.1C EOD ≥ Dis. cur. 0.3C
EOD ≥ Dis. cur. 0.5C EOD ≥ Dis. cur. 1.0C EOD.
Copyright © Huawei Technologies Co., Ltd.