Bypass Settings
Issue 03 (2020-01-10)
Item
Description
overvoltage recovery is set to
Disable, the bus overvoltage
alarm cannot be automatically
cleared, and the rectifier and
inverter cannot automatically
start.
Bus overvolt.
If Bus overvoltage recovery is
recovery time
set to Enable, the bus
overvoltage alarm is
automatically cleared, and the
rectifier and inverter
automatically start when the bus
voltage recovers (less than 420
V) within Bus overvolt.
recovery time.
Capacitor
If Capacitor failure detection is
failure
set to Enable, the power module
detection
(power unit) performs inverter
capacitor fault detection based on
the settings of Capacitor failure
detection upper limit and
Capacitor failure detection
lower limit. If the power module
determines that the inverter
capacitor is faulty, it shuts down
the inverter to prevent the fault
from expanding.
Item
Description
BPM mode
Specifies whether to start bypass
upon BPM
mode when overtemperature
overtemp.
occurs.
Lightload BPM
Enable or disable the light load
cur. eql. detect
bypass current imbalance alarm.
If this parameter is set to Enable,
the load is light (less than 30%
load), and the load rate of a
certain rack is less than 10%, the
system will generate a bypass
current imbalance alarm and
cannot enter the ECO mode. If
this parameter is set to Disable,
the preceding detection is not
performed. Whether the bypass
current is imbalanced does not
affect the ECO bypass mode.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
5s
5s, 1 min, 5 min,
10 min
Disable
Disable, Enable
Default Value
Value Range
Enable
Disable, Enable
Enable
Disable, Enable
121