Battery Settings
Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge
time. When you set battery parameters, note the following:
Issue 03 (2020-01-10)
Retain default settings for Chg. cur. limiting coef. and Cell float voltage. Only
professional maintenance personnel are allowed to change the settings.
When you set parameters, ensure the following: Chg. cur. limiting coef. > Transfer-to-
equalized charging cur. coef.
Single batt. float chg. voltage deviation alarm thres. and Single batt. dis. voltage
deviation alarm thres. are used to check whether the batteries in each battery string have
the same charge voltage and discharge voltage. When a value exceeds the specified range,
an alarm is generated. The calculation formula is (Charge/Discharge voltage – Average
voltage)/Average voltage x 100%. The charge/discharge voltage and average voltage are
obtained from the BMU. If the BMU is not configured, these two parameters do not need
to be set.
Item
Description
Float volt.
If this parameter is set to Enable,
temp. comp.
the float voltage is calibrated
based on the battery temperature
when a battery temperature
sensor is connected. The
parameter is configurable in any
mode.
Float volt.
Calibration coefficient during
temp. comp.
float voltage temperature
compensation.
coef.
(mV/° C· cell)
Float Chg temp
Indicates the reference
comp center
temperature during temperature
(° C)
compensation of the float
charging voltage.
Automatic
If this parameter is set to Enable,
equalized
the UPS automatically changes
charging
the battery management status to
equalized charge based on the
charge current and float charge
time.
Transfer-to-
The battery enters equalized
equalized
charge state when the battery
charging cur.
current exceeds this parameter
coef. (C10)
value.
SOC to start
If the SOC is lower than the
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Enable
Disable, Enable
3.3
0.0–6.0
25
20–30
Enable
Disable, Enable
0.05
0.02–0.08
70
0–100
122