Precautions For Battery Maintenance; Monthly Maintenance - Huawei UPS5000-E-400K Series User Manual

60 kva power modules
Table of Contents

Advertisement

UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)

6.2.1 Precautions for Battery Maintenance

6.2.2 Monthly Maintenance

Table 6-5 Monthly maintenance
Item
Battery
management
alarm
Battery
appearance
Battery
operating
temperature
Charge voltage
of battery string
Issue 05 (2019-12-24)
Wrap tools with insulation tape to prevent electric shock.
Protect your eyes with relevant devices and apply other protective measures.
Wear insulated gloves and a protective coat in case of electrolyte overflow.
When moving batteries, avoid handling the battery upside down, handle batteries gently,
and pay attention to personal safety.
Keep the battery switch off when installing or maintaining the batteries.
Before battery maintenance, get the tools, such as handles, insulated. Do not place other
objects on the top of batteries.
Never use any organic solvent to clean batteries.
Never try to remove the safety valve or pour anything into batteries.
Never smoke or have an open flame around batteries.
After battery discharge, charge the battery in time to maintain a good service life.
Only professionals are allowed to perform the maintenance tasks.
Expected Result
No battery management alarm is
generated.
1. The surface is clean and tidy
without stains.
2. The battery terminals are
intact.
3. Batteries are free from damage
and cracks.
4. Batteries are free from acid
leakage.
5. Batteries are not deformed or
bulged.
1. The ambient battery
temperature is 25± 5° C.
2. The battery operating
temperature is lower than
battery temperature +20° C.
3. Battery charge and discharge
conditions meet the
requirements specified in the
battery specifications.
Equalized charging voltage:
(2.35 V/cell ± 1%) x number of
battery cells
Copyright © Huawei Technologies Co., Ltd.
6 Routine Maintenance
Troubleshooting
Identify the cause of an alarm
based on the alarm information.
If the battery appearance is
abnormal, contact Huawei
technical support.
1. Identify the cause of an
abnormal battery operating
temperature.
2. If the fault persists, contact
Huawei technical support.
1. If the voltage drop between the
battery string output terminals
and the battery input terminals
at the UPS side is greater than
188