Communication Settings - Huawei UPS5000-E-400K Series User Manual

60 kva power modules
Table of Contents

Advertisement

UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
Item
Bat mode shut
Backup time
warning
Remain. cap.
warning
Intelligent
hibernation
Thres. of low
batt. SOC over
dry contact (%)
Thres. of low
batt. volt. over
dry contact
(V/cell)

4.2.2.2 Communication Settings

Figure 4-48 Communication settings
Issue 05 (2019-12-24)
Description
the rack.
In battery mode, the UPS can
automatically power off
according to the preset shutdown
delay time. If the parameter is
disabled, this function is not
available.
An alarm is generated if this
parameter is set to Enable and
the backup time is less than the
warning threshold.
An alarm is generated if this
parameter is set to Enable and
the remaining capacity is less
than the warning threshold.
If this parameter is set to Enable,
the intelligent battery hibernation
function is enabled.
If an output dry contact is set to
Low battery SOC, and the
battery SOC is lower than this
threshold, the output dry contact
will output signals.
If an output dry contact is set to
Batt. Volt. Below Threshold,
and the battery voltage is lower
than this threshold, the output dry
contact will output signals.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable, Enable
Disable
Disable, Enable
Disable
Disable, Enable
Disable
Disable, Enable
75
5–80
1.70
1.70–2.10
144