4.2.2.4 Communication Settings

Figure 4-54 Communication settings
Issue 02 (2020-01-10)
Item
Description
exceeds the charging capacity of
the rack.
Bat mode shut
In battery mode, the UPS can
automatically power off
according to the preset shutdown
delay time. If the parameter is
disabled, this function is not
available.
Backup time
An alarm is generated if this
warning
parameter is set to Enable and
the backup time is less than the
warning threshold.
Remain. cap.
An alarm is generated if this
warning
parameter is set to Enable and
the remaining capacity is less
than the warning threshold.
Intelligent
If this parameter is set to Enable,
hibernation
the intelligent battery hibernation
function is enabled.
Thres. of low
If an output dry contact is set to
batt. SOC over
Low battery SOC, and the
dry contact (%)
battery SOC is lower than this
threshold, the output dry contact
will output signals.
Thres. of low
If an output dry contact is set to
batt. volt. over
Batt. Volt. Below Threshold,
dry contact
and the battery voltage is lower
(V/cell)
than this threshold, the output dry
contact will output signals.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable, Enable
Disable
Disable, Enable
Disable
Disable, Enable
Disable
Disable, Enable
75
5–80
1.70
1.70–2.10
121