PSEN cs6.11n
Wiring
Please note:
}
Information given in the "Technical details" must be followed.
}
The power supply must meet the regulations for extra low voltages with protective sep-
aration (SELV, PELV).
}
The inputs and outputs of the safety switch must have a protective separation to
voltages over 60 VDC.
}
The supply voltage to the safety switch must be protected with a 2 A to 4 A quick-acting
fuse.
}
Ensure the wiring and EMC requirements of EN 60204-1 are met.
Pin assignment, connector and cable
PIN
1
2
3
4
5
The wire colour also applies for the cable available from Pilz as an accessory.
Operating Manual PSEN cs6.11n
1004127-EN-03
INFORMATION
Only use safety relays with a 24 VDC supply voltage. Safety relays with a
wide-range power supply or in AC device versions have internal potential
isolation and are not suitable as evaluation devices.
4
3
5
2
1
Pin
designation
Function
A1
+24 V UB
12
Output, channel1
A2
0 V UB
22
Output, channel2
Y32
Signal output
5-pin M12 male connector
Wire colour
brown
white
blue
black
grey
13