PSEN sl-1.0p 1.1/1.1 VA
Max. lateral offset: 3 mm
}

Wiring

Please note:
You must comply with the specifications stated in the technical details (see Technical
}
details:
actuator [
plate [
The power supply must meet the regulations for extra low voltages with protective sep-
}
aration (SELV, PELV).
The inputs and outputs of the safety switch must have a protective separation to
}
voltages over 60 VDC.
Ensure the wiring and EMC requirements of EN 60204-1 are met.
}
When connecting in series, make sure you comply with the wiring technology require-
}
ments (DIN EN 60204-1) and manipulation protection requirements (EN ISO 14119).

Guidelines for cable length

The max. cable length depends on the voltage drop at the safety switches. The level of
voltage drop is determined by the:
Cable resistance
}
Current of the device and the current load of the outputs
}
If the level of the supply voltage at the device connector falls below the minimum permitted
value (see Technical details:
ing actuator [
plate [
an error when guard locking.
Operating Manual PSEN sl-1.0p 1.1/1.1 VA
1003821-EN-12
System with normal acutator [
30],
System with normal actuator and stainless steel base
34]).
INFORMATION
Only use safety relays with a 24 VDC supply voltage. Safety relays with a
wide-range power supply or in AC device versions have internal potential
isolation and are not suitable as evaluation devices.
System with normal actuator [
30],
System with normal actuator and stainless steel base
34]), the electromagnet is no longer activated reliably. The "Lock" LED registers
27],
System with free-moving
27],
System with free-mov-
12