Table 3-8: Ups Power Cable Terminations - Eaton 93PR User And Installation Manual

500 kw
Table of Contents

Advertisement

See the following table for power cable terminations.

Table 3-8: UPS Power Cable Terminations

Terminal function
AC input to UPS rectifier MAINS INPUT L1,L2,L3,N M12
AC input to bypass
UPS output
DC input from external
battery to UPS
Protective Earth
External overcurrent protection is not provided by this product, but is required by codes. Refer to Table
Minimum recommended multi-core cable and fuse sizes for wiring requirements. If an output lockable disconnect
is required, it is to be supplied by the user.
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings
from Table
local installation rules.
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current val-
ues for AC output to critical load shown in Table
age. The recommended line-to-line load unbalance is 50 % or less.
Source Protection for the AC Input to Bypass should suit the characteristics of the load and take account of
effects such as Inrush or Starting Current. Bypass and output overcurrent protection and bypass and output
disconnect switches are to be provided by the user.
For UPS wiring diagrams, see Chapter
28
Terminal
BYPASS
INPUT
OUTPUT
BAT
PE
NOTE
CAUTION
3-5
: Rated and maximum currents for rated power and voltage in accordance with the national and
Eaton 93PR 500 kW UPS
User's and Installation Guide
Bolt
Function
Specifications
L1,L2,L3,N M12
L1,L2,L3,N M12
battery+
M12
battery–
PE
M12
3-5
: Rated and maximum currents for rated power and volt-
2.1
Looking inside the UPS system.
Bolt
Tighteningtorque
Diameter
Nm
14mm
76 (Nm)
14mm
76 (Nm)
14mm
76 (Nm)
14mm
76 (Nm)
14mm
76 (Nm)
3-6
: