MESSAGE
UPS LDEV <nnn> reports UPS "High Ambient Temperature"
condition. (UPSERR 0199)
CAUSE
The specified PowerTrust unit reported a "High Ambient Temperature"
condition. The PowerTrust unit has detected an abnormally high temperature
in the PowerTrust unit hardware. If the temperature rises further, the
PowerTrust unit may reach a "High Ambient Temperature Shutdown"
condition. The computer room temperature is too high, or there may be a
hardware malfunction in the PowerTrust unit.
ACTION
If the computer room has become too warm, take steps to cool the room. If
room temperature is not the problem, then replace the faulty PowerTrust unit.
MESSAGE
UPS LDEV <nnn> reports UPS "Battery Test Fail" condition.
(UPSERR 0200)
CAUSE
The specified PowerTrust unit reported a "Battery Test Fail" condition. This is
a hardware malfunction within the PowerTrust unit hardware. The
PowerTrust unit logic perceives that the PowerTrust unit battery is not
working properly.
ACTION
Call HP Service.
MESSAGE
UPS LDEV <nnn> reports UPS "High Battery Voltage" condition.
(UPSERR 0201)
CAUSE
The specified PowerTrust unit reported a "High Battery Voltage" condition.
This is a hardware malfunction within the PowerTrust unit hardware. The
PowerTrust unit logic perceives that the PowerTrust unit battery is not
working properly.
ACTION
Call HP Service.
Appendix B
MPE/iX UPS Monitor Error Messages
Alarm Status Messages
B-9