b. Output Wiring:
The output terminals can accommodate stranded copper wire with a range of 14
AWG to 4 AWG (2.5 mm
Output wiring should be sized based on input current requirements of the load
equipment, in accordance with local codes.
2. This UPS may be wired with either cords or conduit.
Installing cords:
a. The strain relief can accept 18.0 mm (0.709 in) to 25.4 mm (1.00 in) diameter
cords.
b. If not already done, strip the outer cord covering 15.2cm (6 in) and strip the wires
12.7mm (.50 in).
c. Insert each cord into the strain relief bodies that are attached to the conversion
plate. The cords should enter from the side of the plate that has printing on it.
The input cord goes into the strain relief on the left (under the printing). The
output cord goes into the strain relief on the right.
d. Position each cord so that the outer covering of the cords protrudes 2.54 cm (1.0
in) past the inside end of the strain relief bodies. Hand tighten both bushings to
secure the cords.
Installing conduit connectors:
The plate has 1 23/64' holes that can accommodate conduit connectors in place of
strain reliefs. Remove the strain reliefs and replace them with suitable conduit
connectors. Attach the conduits to the connectors and insert the connecting wires
into the conduits with the wires protruding through the conversion plate.
3. Attach the conversion plate to the rear panel using the four Torx screws supplied in
the kit. Make certain that the conversion plate is positioned over the opening in the
rear panel.
4. Connect the wires as follows:
Input wiring for worldwide (hardwired) version (200-240V/50 or 60 Hz):
Line (or Line 1): Connect wire to the L1 IN terminal
Neutral (or Line 2) Connect wire to the L2/N IN terminal
Protective Earth Ground: Connect the GREEN or GREEN/YELLOW wire to
the protective earth terminal marked with the following symbol:
Appendix D
2
2
- 16 mm
).
Field Replaceable Units
Removal and Replacement Procedures
D-15